Transformer sizing calculation

 • Transformer standard rating or size available in the market :

   63 kVA

   80 kVA

   100 kVA

   125 kVA

   160 kVA 

   200 kVA

   250 kVA

   315 kVA

   400 kVA

   500 kVA

   630 kVA

   750 kVA

   1000 kVA

    1250 kVA

    1500 kVA

    1750 kVA

    2000 kVA

    2500 kVA

    3150 kVA

    4000 kVA

    5000 kVA

    6300 kVA

    7500 kVA

    10000 kVA.


• Demand Factor is depend on client.

     D.F. = 0.6, 0.7, 0.8, 0.9

    

    D.F = P.D÷T.C.L


therefore, P.D = D.f × T.C.L


• we will get Peak Demand (P.D) in KW


• then, KVA = KW÷ P.F.  (P.F = 0.8)


• After that, KVA/0.7      (0.7= Loading factor)


Therefore, the result will be our transformer value or selection.


Note : In future expansion multiply by 1.25



Example : 

                  Building.      Each KW.        Qty flat

                     2BHK.            4 KW.            12 No.

                     3BHK.            6KW.             12 No.

                 Com. Load.       20 KW.            --


• Calculate total KW

              4KW × 12 = 48 KW

              6KW × 12 = 72 KW

               20KW × 1 = 20 KW

 Therefore,    T.C.L = 140 KW


• D.F. = 0.6 (or) 60% we take


     P.D = D.F × T.C.L 

            = 0.6 × 140 = 84 KW


• KVA = KW÷ P.F = 84 ÷ 0.8 = 105 kVA


• Loading factor = 105÷0.7 = 150 KVA


• Therefore, 150 rating comes to load

                 So, 160 KVA rating transformer is   recommended for building.