• Transformer standard rating or size available in the market :
63 kVA
80 kVA
100 kVA
125 kVA
160 kVA
200 kVA
250 kVA
315 kVA
400 kVA
500 kVA
630 kVA
750 kVA
1000 kVA
1250 kVA
1500 kVA
1750 kVA
2000 kVA
2500 kVA
3150 kVA
4000 kVA
5000 kVA
6300 kVA
7500 kVA
10000 kVA.
• Demand Factor is depend on client.
D.F. = 0.6, 0.7, 0.8, 0.9
D.F = P.D÷T.C.L
therefore, P.D = D.f × T.C.L
• we will get Peak Demand (P.D) in KW
• then, KVA = KW÷ P.F. (P.F = 0.8)
• After that, KVA/0.7 (0.7= Loading factor)
Therefore, the result will be our transformer value or selection.
Note : In future expansion multiply by 1.25
Example :
Building. Each KW. Qty flat
2BHK. 4 KW. 12 No.
3BHK. 6KW. 12 No.
Com. Load. 20 KW. --
• Calculate total KW
4KW × 12 = 48 KW
6KW × 12 = 72 KW
20KW × 1 = 20 KW
Therefore, T.C.L = 140 KW
• D.F. = 0.6 (or) 60% we take
P.D = D.F × T.C.L
= 0.6 × 140 = 84 KW
• KVA = KW÷ P.F = 84 ÷ 0.8 = 105 kVA
• Loading factor = 105÷0.7 = 150 KVA
• Therefore, 150 rating comes to load
So, 160 KVA rating transformer is recommended for building.