Short circuit calculation

 • Breaking capacity :

     The maximum short circuit current which can be safely stop by C.B. is called Breaking capacity.


C.B. : Protection from overload and short circuit.


Breaking capacity :

  MCB         MCCB          ACB          Fuse

  6KA            25KA        50KA          125KA

  10KA          36KA        65KA

  15KA          50KA        70KA

                      65KA        95KA

                      70KA


Example :

      SLD


 


 


- S1

     % z is not ohm's value we have convert

% value to Ω value.


→Z(Ω) = 10%Z × (kv)2/ KVA


     = 10×6×(0.433)×(0.433)/ 1000


       Z(Ω) = 0.01124


Isc = V÷√3×Z(Ω)

        = 433÷√3×0.01124

        = 433÷ 0.01946

        = 22,250.77 A


       22,250.77÷1000=22.250KA


Peak s/c = 2.5×Initial value

                = 2.5× 22.50

                = 55.62 KA

Therefore, the breaking capacity is 65KA.


S2 :

    We have to convert % × to (Ω)value


X(Ω) = 10× % × (xv)2/ KVA


         = 10× 20× (0.433)2/ 1000

         = 37.4978/ 1000


X(Ω) = 0.03749Ω

     

  For LT D.G : R(Ω) = 0.15× (Ω)

                                 = 0.15× 0.03749

                         R(Ω) = 0.0056235


                  Z = √Rsq.+ Xsq.

                     = √ (0.00562)+(0.0374)

                 Z = 0.04302



Isc =    V / √3 × Z(Ω)

       =  433/ 1.733× 0.04302

       =  433/ 0.07451


       = 5811.300 A

       = 5811.300/1000= 5.8113A


Peak s/c = 2.5 × Initial value

                = 2.5 × 5.8113

                = 14.528 KA

Therefore, the breaking capacity is 25 KA.


S3 :

     500kw

       950A - 400sq.mm- 0.10Ω/km

                     No. Of cable is 3


R(Ω) = length (mts) × Î©/km/ 1000× no.of cable


= 50 × 0.10/ 1000×3 

= 5/3000

= 0.00166Ω


Isc = V / √3×Z(t/f) + Z(cable)

      = 433 / √3 × (0.01124+0.00166)

      = 433 / 1.732+0.0129

      = 433 / 0.0223

      = 1941.704 A

         1941.704/1000 = 19.417 KA


Peak S/c current = 2.5 × 19.417

                               = 48.54KA


  Therefore, the breaking capacity is 50KA


S4

     500 kw          length-50mts


      500 × 1.9=  950 A

     400sq.mm - 0.10Ω/km

   (3 no.of cable)


R(Ω) = length (mts) × Î©/km ÷ 1000× no.of cable


        = 50 × 0.10 / 1000×3

        = 5 / 3000 = 0.0016


Isc = V/ √3×Z(t/f)+Z(cable)


       = 433 / 1.733× (0.01124+0.0016)

       = 433 / 1.733× 0.01284

       = 433 / 0.02223 

       = 19,478.182A

    

→ 19,478.182/ 1000

 = 19.478 KA


Therefore, breaking capacity is 25KA.