Circuit Breaker sizing and calculation

 • Standard rating available :

     0 - 63 A → MCB

     80 - 630 A → MCCB

     800 and above → ACB


    5 A

    10 A

    16 A

    20 A

    25 A

    32 A

    40 A

    50 A

    63 A

    80 A

    100 A

    125 A

    160 A

    200 A

    250 A

    320 A

    430 A

    500 A

    630 A

    800 A

    1000 A

    1250 A

    1600 A

    2000 A

    2500 A

    3200 A

    4000 A

    5000 A

    6300 A

                  For 3 - Ø

- If the rating in KW multiply with 1.9

                     KW × 1.9 = A

- If the rating in KVA multiply with 1.4

                     KVA × 1.4 = A

- If the rating in HP multiply with 1.5

                     HP × 1.5 = A

- If the rating in KVAR multiply with 2

                 KVAR × 2 = A


             For 1 - Ã˜

- If the rating in KW multiply by 6 @ P.F. 0.8

              = KW × 6 = A

- If the rating in KW multiply by 8 @ P.F. 0.6

              = KW × 8 = A


Example

    If we selected a 160 kVA transformer


For 160 kVA , 

                       kVA × 1.4

                       160 × 1.4 = 224 A

         

For C.B again we will multiply by 1.25 safety factor.

               224 × 1.25 = 280 A

Therefore, 280 A for 320 A MCCB recommend


Example 2


       For 500 kVA transformer,

                 kVA × 1.4

                 500 × 1.4 = 700 A

       Safety factor is 1.25

                   700 × 1.25 = 875A

Therefore, 

            For 875 A we selected 1000 A ACB is recommended.



• wire / cables with amper rating : 


   1.5 sq.mm -- 5 A MCB

   2.5 sq.mm -- 10 A MCB

   4 sq.mm ---  25 A MCB

   6 sq.mm ---  32 A MCB

   10 sq.mm ---  40 A MCB

   16 sq.mm ----  63 A MCB


Therefore, this are MCB rating and wire size for power and light system.